AVKO

PRE-INSULATED PIPE SYSTEMS FOR DISTRICT HEATING NETWORKS


FOR DIRECT BURIAL
Pre-insulated piping system for CENTRALIZED DISTRICT HEATING

PRE-INSULATED ELBOW 90°, 45°

  PRE-INSULATED ELBOW 45°PRE-INSULATED ELBOW 45°

PRE-INSULATED ELBOW 90° PRE-INSULATED ELBOW 90°

DN

d

D

L

mm

mm

mm

20

26,9

90

1000

25

33,7

90

1000

32

42,4

110

1000

40

48,3

110

1000

50

60,3

125

1000

65

76,1

140

1000

80

88,9

160

1000

100

114,3

200

1000

125

139,7

225

1000

150

168,3

250

1000

200

219,1

315

1000

250

273,0

400

1000

300

323,9

450

1200

350

355,6

500

1200

400

406,4

560

1500

500

508,0

630

1500

600

610,0

800

1500

700

711,0

900

1500

800

813,0

1000

1500 

DN        – Nominal diameter (mm)

d          – Steel pipe outside diameter (mm)

D          – Casing PE pipe outside diameter (mm)

L          – Arms length (mm)

Bending radius:

- Welded elbows                    R = 1,5 d

- Cold bent elbows                R = 2,5 d

Other sizes – on request and after discussion.

 

Raw materials

Carrier steel pipe is manufactured acc.:

- EN 10216-2 or another equivalent norm regarding seamless pipes, steel grade P235GH .

- EN 10217-1 another equivalent norm regarding longitudinally welded pipes, steel grade P235TR1/TR2

- EN 10217-2 another equivalent norm regarding longitudinally welded pipes, steel grade P235GH

- EN 10217-5 another equivalent norm regarding spirally welded pipes, steel grade P235GH

- EN 10220 – steel pipes sizes

Pipe ends are bevelled in order to facilitate welding acc. ISO 6761.

During production, the quality of the welding seam is monitored constantly visually and through non-destructive testing. Finished pipes are subjected to hydro-static testing at 80 bar per 5 sec.

 

HDPE Casing pipe

Otside casing pipe is manufactured from high-density polyethilene with added antioxidants, UV stabilizers and carbon black.

Internal surface of PE pipes is processed with Corona treatment in order to achieve better adhesion with PUR foam.

 

Polyurethane system

AVKO jsc is using polyurethane system with foaming agent cyclopentane. The resulting PUR foam is characterized with very low heat conductivity coefficient  < 0,027 W/mK.